▎Product Introduction :
Studies indicate 1% H₂ purity reduction causes 11% efficiency loss. Impurities (O₂/N₂/CO₂) create safety hazards. H₂ explosion range: 4.1%~74.2% in air (H₂/O₂ mixture).
The RA1630B enables real-time O₂ monitoring in hydrogen-cooled generators for operational safety.
▎Key Features :
1.Intrinsically safe explosion-proof sensor.
2.High accuracy with anti-interference.
3.Automatic drainage system.
4.On-site calibration capability.
5.Sensor protection technology.
▎Technical Specifications :
Parameter |
Value |
Range |
(0~2)% O₂ |
Accuracy |
±0.03% |
Repeatability |
±0.01% |
Response Time |
20 s |
Analog Output |
(4~20) mA, max load 800Ω |
Power Supply |
24 VDC or 220 VAC |
Alarm Output |
DC24V 1A (two programmable alarm outputs) |
Explosion-proof Rating |
Ex ia IIC T4 Ga |

Phone:+86 400 659 6699
E-mail:info@relations.com.cn
Address: