▎Product Introduction :
The Linux-based RA912F (8-in-1) SF₆ Gas Comprehensive Analyzer combines multiple intelligent functions with premium design for rapid SF₆ component analysis, simultaneously measuring humidity, purity and decomposition products (SO₂, H₂S, CO, H₂) plus CF₄ and air/O₂ content.
▎Key Features :
1.Dual-channel automatic flow control.
2.BPS battery power supply.
3.Humidity PPMS conversion compliant with DL/T 506-2018.
4.Waterproof telescopic case design.
5.Automatic data locking when stable/qualified.
▎Technical Specifications :
Humidity Td(Capacitive) |
|
Range |
(-60~+20) °C DP |
Maximum Permissible Error |
±2°C DP |
Response Time |
≤3 min |
SF₆ Purity |
|
Range |
(0~100) % or (90~100) % (vol) |
Maximum Permissible Error |
±0.5% (vol) |
Response Time |
≤40 |
Air(O₂ Conversion) |
|
Range |
(0~5000) μL/L (21% O₂ conversion) |
Maximum Permissible Error |
±2.5%F.S |
Response Time |
≤40 |
CF₄ Detection |
|
Range |
(0~2000) μL/L |
Maximum Permissible Error |
±2.5%F.S |
Response Time |
≤40 |
SO₂ Detection |
|
Range |
(0~100) μL/L |
Maximum Permissible Error |
(0~10) μL/L: ±0.5 μL/L; (10~100) μL/L: ±5% |
Response Time |
≤40 |
H₂S Detection |
|
Range |
(0~100) μL/L |
Maximum Permissible Error |
(0~10) μL/L: ±0.5 μL/L; (10~100) μL/L: ±5% |
Response Time |
≤40 |
CO Detection |
|
Range |
(0~500) μL/L |
Maximum Permissible Error |
(0~50) μL/L: ±2 μL/L; (50~500) μL/L: ±4% |
Response Time |
≤40 |
H₂ Detection |
|
Range |
(0~100) μL/L |
Maximum Permissible Error |
±5%F.S |
Response Time |
≤60 |

Phone:+86 400 659 6699
E-mail:info@relations.com.cn
Address: